TERMOTECH Termoplasty system structure

Preinsulated pipeline system components

  • composite pipes

  • composite fittings

  • connector unit

  • fasteners

  • additionally pipes, fittings and valves without preinsulation

Structure

budowa rury preizolowanej Termotech

ATTENTION: Duct can be double - details on request.

Additional elements of the preinsulated pipeline TERMOTECH Termoplasty system:

  • electric heating cable

  • tightness monitoring

Conduit pipe

Material Rated operating temperature
PE-HD 100 -50°C ÷ +60°C
PVC-U 0°C ÷ +60°C
PP-H 0°C ÷ +80°C
PB 0°C ÷ +95°C
ABS -40°C ÷ +60°C
PVC-C 0°C ÷ +90°C
PVDF -40°C ÷ +140°C

Thermal insulation

Insulation in the form of PUR polyurethane foam is characterized by very goos thermal insulation properties which also greatly increases composite material stiffness.

Basic parameters:

  • thermal conductivity ratio λ<0.027W/mK at 50oC

  • foam core density ρ>45kg/m3

Sleeve pipe

Depending on the type of system and user preference, 3 types of sleeve pipes are possible:

  • hard polyethylene (PE-HD) pipe of density of ρ>944kg/m3 and corona-treated internal surface meeting the requirements of PN-EN 253 standard.

  • SPIRO spiral wound pipes of galvanized sheets as per PN-81/H-92125

  • SPIRO spiral wound pipes of aluminum sheets as per PN-87/H-92833

 